火灾自动报警系统工程规范外文翻译资料

 2022-02-21 20:56:50

Engineering Specification for Fire Alarm System

  1. System Description
    1. System Components

The FAS comprises the following equipment:

  • Fire Alarm Controller
  • Hardware Control Panel
  • Fire Telephone Panel
  • Programmable Alarm Trip
  • Fire Alarm Control Cabinet
  • Fire Display Panel
  • Graphical Display Device
  • Fire Detection Devices
  • Module
  • Marshalling Cabinet
  • Junction Box
  • Module Junction Box
  • Alarm Devices
  • Fire Telephone
  • DC Power Supply
    1. System Architecture

The FAS includes a fire alarm control cabinet. The cabinet located in the central control room of central control building. The field Devices and components related to the FAS will be connected to the FAS marshalling cabinet, and connected to the fire alarm control cabinet via the system cable, and the marshalling cabinet is located in the plant room of CCB.

The FAS consists of one fire alarm controller, one fire telephone panel, one hardware control panel and two alarm trips. The equipments shall be installed in the fire alarm control cabinet, and a DC power supply and a battery shall be installed in the fire alarm control cabinet, too.

A graphical display device shall be located in the CCR, and the device shall be directly connected to the fire alarm controller.

    1. System Function

The FAS is used for the detection of fires and to notify personnel in the centre control room at the earliest possible stage, give the alarm to evacuate people, and activate the fire protection facilities automatically to prevent fire from spreading. The alarm shall be initiated automatically and/or manually (manual call point).

When the fire alarm controller receives the alarm signal of detector, manual call point or other alarm signals, it will activate loudspeaker in PA/GA system, indicate the site of fire, shut off the HVAC equipment power etc, receive feedback signal, and switch on the emergency lights and evacuating lights, too.

All logs of fire alarm, system fault, communication failure and operation logs will be printed and be recorded in the fire alarm controller.

In case of fire, the equipment layout for relative unit shall be indicated on display of GDD, and the alarm position shall blink automatically.

All logs of fire alarm, system fault, communication failure and operation logs will be recorded in the GDD, and the logs in GDD shall be kept at least for two years.

Three programmable alarm trips is used for viewing water level of unit 13 fire water tanks and unit 14 fire water buffer pit, and output 4 loops alarm signals to FAS.

    1. Test Report for Fire Product

The following fire products shall be certified in accordance with requirements of Chinese correlative standards and bear the respective NFEP test report numbers:

  • Fire Alarm Controller
  • Smoke Detector
  • Heat Detectors
  • Heat Detectors Wire
  • Module
  • Manual Call Point
  • Aspirating Smoke Detector
    1. China Compulsory Certification (CCC)

The following fire products shall be certified in accordance with requirements of Chinese correlative standards and bear the respective CCCF certification numbers

  • Fire Alarm Controller
  • Smoke Detector
  • Heat Detectors
  • Manual Call Point
    1. Hazardous Areas

The field equipment selected shall be certified for the hazardous area where it is installed.

The field equipment shall be certified in accordance with the requirements of recognized Chinese authorities and bear the respective NEPSI certification numbers.

    1. Interface with Other Systems

Gas detector is not a part of the FAS, Gas detectors are classified as field instrumentation and connected to DCS. FAS shall receive gas alarm signals from DCS via 24V relay.

The FAS shall have the interfaces with the following system:

  • HVAC System
  • Access Control System
  • Power Distribution System
  • Smoke Exhaust System
  • Fire Fighting Water System
  • Fire Fighting Foam System
  • Gas Detection System
  1. System Installation
    1. Installation of FAS Devices

If there is no special instruction of installation of the FAS devices, the installation height relative to the floor height shall follow the list below:

Field Module Junction Box (Bottom): 1.4m

Junction Box (Bottom):1.4m

Fire Display Panel (Bottom):1.45m

Fire Telephone (Bottom):1.4m

Manual Call Point (Bottom): 1.4m

Smoke Detector: Ceiling Installation

Smoke Detector (Under raised floor): Closed to the floor

Heat Detector: Ceiling Installation

All the modules shall be installed in the field module junction boxes.

    1. Cable Laying
    剩余内容已隐藏,支付完成后下载完整资料


    火灾自动报警系统工程规范

    1.系统描述

    1.1系统组件

    FAS包括以下设备:(1)火灾报警控制器;(2)硬件控制面板;(3)消防电话面板;(4)可编程报警跳闸;(5)火灾报警控制柜;(6)消防显示面板;(7)图形显示设备;(8)火灾探测设备;(9)模块;(10)编组内阁;(11)接线盒;(12)模块接线盒;(13)报警设备;(14)消防电话;(15)直流电源。

    1.2系统架构

    FAS包括火警控制柜。柜体位于中央控制楼的中央控制室。现场与FAS相关的设备和组件将连接到FAS编组柜,并通过系统电缆连接到火警控制柜,编组柜位于CCB的工厂房间。

    FAS由一个火警控制器,一个消防电话面板,一个硬件控制面板和两个警报跳闸组成。设备应安装在火灾报警控制柜内,火灾报警控制柜内还应安装直流电源和电池。

    图形显示设备应位于CCR中,设备应直接连接到火警控制器。

    1.3系统功能

    FAS用于火灾的检测,并尽可能早地通知中心控制室的人员,发出警报以疏散人员,并自动启动消防设施以防止火势蔓延。警报应自动和/或手动启动(手动呼叫点)。

    当火灾报警控制器接收到探测器,手动报警点或其他报警信号的报警信号时,它将激活PA / GA系统中的扬声器,指示火灾现场,关闭HVAC设备电源等,接收反馈信号,并切换在应急灯和疏散灯上也是如此。

    将打印所有火灾报警,系统故障,通讯故障和操作日志,并记录在火灾报警控制器中。

    发生火灾时,相关单元的设备布局应在GDD显示屏上显示,报警位置应自动闪烁。

    火灾报警,系统故障,通信故障和运行日志的所有日志将记录在GDD中,GDD中的日志应至少保存两年。

    三个可编程报警跳闸用于查看13单元消防水箱和单元14消防水缓冲坑的水位,并输出4个循环报警信号到FAS。

    1.4消防产品检测报告

    以下消防产品应按照中国相关标准的要求进行认证,并具有相应的NFEP测试报告编号:(1)火灾报警控制器;(2)烟雾探测器;(3)热探测器;(4)热探测器线;(5)模块;(6)手动呼叫点;(7)吸气式烟雾探测器。

    1.5中国强制认证(CCC)

    以下消防产品应按照中国相关标准的要求进行认证,并具有相应的CCCF认证编号:(1)火灾报警控制器;(2)烟雾探测器;(3)热探测器;(4)手动呼叫点。

    1.6危险区域

    所选的现场设备应在其安装的危险区域进行认证。现场设备应按照中国认可机构的要求进行认证,并具有相应的NEPSI认证编号。

    1.7与其他系统的接口

    气体探测器不是FAS的一部分,气体探测器被归类为现场仪表并连接到DCS。FAS应通过24V继电器接收DCS的气体报警信号。

    FAS应具有以下系统的接口:(1)暖通空调系统;(2)门禁系统;(3)配电系统;(4)排烟系统;(5)消防水系统;(6)消防泡沫系统;(7)气体检测系统。

    2.系统安装

    2.1安装FAS设备

    如果没有安装FAS设备的特殊说明,相对于地板高度的安装高度应遵循以下列表:

    现场模块接线盒(底部):1.4米

    现场模块接线盒(底部)

    1.4米

    接线盒(底部)

    1.4米

    消防显示屏(底部)

    1.45米

    消防电话(底部)

    1.4米

    手动呼叫点(底部)

    1.4米

    烟雾探测器

    天花板安装

    烟雾探测器(高架地板下)

    靠近地板

    所有模块应安装在现场模块接线盒中。

    2.2电缆敷设

    室外电缆应铺设在地下电缆或电缆桥架中,室内电缆应铺设在地面导管或隐蔽导管内,隐蔽导管应铺设在不可燃结构层内,保护层厚度不小于30mm;表面导管(包括在天花板上)应涂上三层防火涂料。如果没有特殊说明,室内电缆应铺设在镀锌焊接钢管中。以下是所有装置铺设的电缆的信息。

    单位号

    单位名称

    表面导管(室内电缆)

    隐藏式导管(室内电缆)

    02

    警卫室1

    radic;

    03

    警卫室2

    radic;

    11/12

    生产管理员建筑和食堂

    radic;

    13

    消防水泵房和坦克

    radic;

    16

    维修车间

    radic;

    19

    废水检查坑

    radic;

    51

    35KV变电站

    radic;

    53

    中央控制大楼

    radic;

    55

    冷水机组

    radic;

    56

    冷却塔机组

    安装现场设备时,电缆红芯应与其正极连接,电缆蓝芯应与其负极连接。

    当管道沿墙壁水平放置时,高度应距离地面至少3米,并避免穿过门窗。

    3.项目范围

    整个网站将包括3个项目。

    项目1

    INFRA项目

    项目2

    AQ项目

    项目3

    tBA项目

    现场设备和与AQ和TBA项目中的FAS相关的系统将连接到INFRA项目中的FAS编组柜,并且编组柜位于CCB的工厂房间。然后,编组柜通过系统电缆连接到CCR的FA控制柜。

    AQ和tBA项目将与INFRA项目共享FA控制柜内的所有设备。

    机柜内的FA控制柜,FA编组柜和设备以及INFRA项目中的现场设备属于INFRA项目。AQ项目中的现场设备属于AQ项目。tBA项目中的现场设备属于tBA项目。

    从AQ项目到INFRA项目的电缆属于AQ项目。从tBA项目到INFRA项目的电缆属于tBA项目。

    与AQ项目的FAS接口是CCB编组柜中的终端。带有tBA项目的FAS接口也是CCB编组柜中的终端。

    4.主要设备规格

    4.1火灾报警控制器:

    (1)非网络模式下的P2P网络框架设计;(2)控制面板容量:4个环路,可扩展至16个环路,每个环路地址不小于200个;(3)黑盒功能,数据存储最多1000条火灾报警记录和其他1000条信息;(4)可连接不超过16套火灾显示板;(5)中文LCD显示,像素不低于240x64;(6)打印中文;(7)具有保护现场设备和电源短路的功能;(8)19#39;标准机柜安装。

    4.2硬件控制面板

    (1)可控制多达32个环路总线或多线路输出设备

    (2)充当键盘锁,防止操作错误。

    (3)每个循环可以作为现场反馈的启动和指示。

    (4)每个回路都具有线路故障的测试功能。

    (5)19#39;标准机柜安装

    4.3消防电话面板

    (1)多线型

    (2)电话录音自动录音,屏幕显示相关信息

    (3)装载能力:24个单位。

    4.4图形显示设备

    (1)可以显示各区域的总体规划和设备方案,可以自由切换

    (2)当软件系统收到报警信号时,相应的点可以精确定位在指示的平面和中心

    (3)报警位置可自动闪烁。在现场设备复位之前,相应的尖端和闪烁将无法恢复和清除。

    (4)两种不同语言的软件界面(中/英文),易于切换。

    (5)包括计算机,软件和通信模块

    4.5消防显示面板

    (1)中文液晶显示屏

    (2)可以显示火灾报警控制器的所有火灾和故障

    4.6可编程报警跳闸

    (1)LED显示屏

    (2)一回路4-20mA输入,回路供电

    (3)4个可编程继电器输出

    5.内阁

    5.1机柜通用规范

    (1)机柜应配备锁。颜色应为RAL 7032。

    门的开启角度gt; 135度。

    (2)机柜应可安装在假地板结构上。

    (3)所有电缆,端子和设备应在每个机柜中唯一标记。

    (4)机柜应根据电信系统的编号规范在前后侧唯一标记。

    (5)电缆从底部进入,应牢固夹紧。

    (6)室内封闭柜的防护等级为IP52。

    (7)设计应提供充分的自然对流通风装置,以防止已安装设备过热。

    (8)所有机柜应在空间和终端中容纳20%的空间容量。

    (9)接地母线(铜)应用于接地。